Climate resilience strategies for schools in mediterranean areas: is it feasible to condition air merely with ventilation?
Paolo Maria Congedo, Andrea Palmieri, Cristina Baglivo · 2025 · 6 citationsRead the paper
Abstract Managing energy costs in school buildings across Italy poses a significant challenge. Over time, various directives have aimed to reduce energy consumption and improve indoor air quality to enhance student and teacher performance. This study offers an innovative analysis of the thermal behavior of a school in a typical Mediterranean climate. The building envelope is designed to meet legal standards for thermal transmittance specific to its Italian climate zone. Using Termolog Epix 15 software, the study conducts dynamic annual and hourly simulations to assess operative temperature and relative humidity in classrooms, with the heating system turned off and varying air exchange rates. The results suggest that optimizing the building envelope can be more effective than installing traditional HVAC systems (heating, ventilation, and air conditioning) in warm climates, demonstrating the effectiveness of a mechanical ventilation system without heating or cooling. By analyzing the PMV (Predicted Mean Vote) and PPD (Predicted Percentage of Dissatisfied) indices, the study demonstrates that it is possible to maintain acceptable thermo-hygrometric comfort through the only ventilation. During winter, with air changes per hour ranging from 1 to 5, classrooms can maintain temperatures between 21 °C and 23 °C, ensuring thermal comfort without heating. Typically, a heating system would operate for approximately 1071 h annually, excluding holidays. However, an effective ventilation system could eliminate the need for heating entirely. While maintaining optimal temperatures in the intermediate months (spring/autumn) and summer is more challenging, this concern is mitigated by the fact that schools are closed during summer holidays.
What the full text shows
Theory or simulation- Classrooms can maintain thermal comfort without heating during winter by modulating ventilation rates. — 21 °C to 23 °C (Air changes per hour between 1 and 5 in a Mediterranean climate)
- A mechanical ventilation system can potentially eliminate the need for a heating system that would otherwise operate for a specific annual duration. — 1071 h annually (Excluding holidays)
- High internal heat gains from occupants and devices can offset heating requirements when paired with a highly efficient building envelope. (Mediterranean climate, heating system turned off)
- Maintaining optimal temperatures is more difficult during intermediate months (spring/autumn) and summer. (Heating and cooling systems turned off)
- Setup
- Prototype school building in Lecce, Italy (Mediterranean climate) with a square floor plan divided into nine 6x6m zones, designed to meet Italian national thermal transmittance limits for climate zone C.
- How
- Dynamic annual and hourly simulations were performed using Termolog EpiX 15 software to assess operative temperature and relative humidity. Thermal comfort was evaluated using UNI EN 16798-1 and UNI EN 7730 standards (PMV and PPD indices).
- Limitations
- Simulation-based study using a simplified regular geometry prototype. · Does not include a heat recovery unit in the most critical condition analyses. · Summer comfort is not addressed due to school holiday closures.
Summarized by Gemma 4 from the open-access full text · 14 Nov 2026. Read it